Materials: copper or stainless steel
Features: With reliable installation, good protection and explosion-proof function.
Applications: The product suitable for clamping and fixing steel wire knit of armoured cable. There is EX for cable core and the enclosure gas sealing protection must be IP66.
EX Mark:EXEII is equal to II2G, EXDII is equal toII2G EXD II (EU standard)
Protection degree:IP66
Usage Place:Hazardous division 1&2, Explosion gas atmosphere class IIA, IIB, IIC.
Thread | Thread Length (mm) | Sealing range of cable dis Ø(mm) A B | Max thickness of steel braid 01(mm) Min Max | Max thickness of steel braid 02(mm) | The diameter of wires (mm) | Max Diameter B(mm) | ||
M20x1.5 | 12 | 6.1-12 | 9.5-17 | 0.1 | 0.4 | 0.96 | 1.8/1.25 | 30 |
M25X1.5 | 16 | 11.1-14 | 18.7-29 | 0.1 | 0.71 | 1.4 | 1.25/1.6 | 43 |
M32X1.5 | 16 | 17-21 | 22.9-35 | 0.1 | 0.7 | 1.4 | 1.6/2 | 50 |
M40X1.5 | 16 | 22-28 | 26-42 | 0.1 | 0.8 | 1.4 | 1.6/2 | 60 |
M50X1.5 | 17 | 29.5-39 | 35.5-48 | 0.2 | 0.63 | 1.4 | 21/2.5 | 65 |
M63X1.5 | 17 | 40.1-51 | 45.6-62 | 0.2 | 0.63 | 1.5 | 2.5 | 80 |
M75X1.5 | 19 | 52.8-63 | 57-74 | 0.3 | 0.81 | 1.5 | 2.5 | 92 |
M100X1.5 | 19 | 70-86 | 76-93 | 0.3 | 0.94 | 1.5 | 3.15 | 117 |
G1/2" | 12 | 3.1-8.6 | 6.1-13.4 | 0.1 | 0.4 | 0.1 | 0.85 | 24 |
G3/4" | 12 | 6.1-11.6 | 9.5-15.9 | 0.1 | 0.7 | 0.9 | 0.9/1.25 | 30 |
G1" | 16 | 11.1-19.9 | 18.7-25 | 0.1 | 0.7 | 1.4 | 1.25/1.6 | 43 |
G1 1/4" | 16 | 17-26.2 | 22.9-30 | 0.1 | 0.7 | 1.4 | 1.6/2 | 50 |
G1 1/2" | 16 | 22-32.1 | 26-35 | 0.1 | 0.8 | 1.4 | 1.6/2 | 60 |
G2" | 17 | 29.5-38.1 | 35.5-45 | 0.2 | 0.63 | 1.4 | 2/2.5 | 65 |
G2 1/2" | 17 | 47.2-50 | 45.6-55 | 0.2 | 0.63 | 1.5 | 2.5 | 80 |
G3" | 19 | 52.8-61.9 | 57-72.1 | 0.3 | 0.81 | 1.5 | 2.5 | 92 |
G4" | 19 | 70-86 | 76-93 | 0.3 | 0.936 | 1.5 | 3.15 | 117 |